☆彩色銀幕,同時顯示諧波和波形+峰值
☆總諧波失真分析THD
☆三相電壓電流不平衡比VUR/AUR
☆計算中線不平衡電流AN
☆捕抓瞬間狀態:
Dip電壓驟降/Swell電壓驟升/Outage斷電
☆大電力配電,穩定供電系統必備儀表
‧適用系統:1P/2W,1P/3W,3P/3W,3P/4W
單相兩線、單相三線、三相三線、三相四線
‧量測功能:
相對相電壓、相對地電壓、相對地電流
相KW/KVA/KVAR/PF、系統KW/KVA/KVAR/PF
系統KWH/KVAH/KVARH/PFH
相位角
‧諧波和波形同時顯示
‧顯示波形最大值
‧總諧波失真分析THD
‧三相系統參數的圖相圖顯示
‧三相不平衡電壓電流比VUR/AUR及不平衡因素
‧經中性線計算不平衡電流
‧以設定之百分比,捕獲瞬間事件
(驟降,驟升和停電)
‧可設定比例:
CT比流器(1-600)、PT比壓器(1-1000)
‧高ACV輸入阻抗10MΩ
‧符合安全規範IEC 1010,CAT III 600V
☆標配CP-1201電流鉤頭*3
可夾最大尺寸:直徑50mm
量測電流:AC20A/200A/1200A
☆多種電流鉤頭輸入電壓可選擇:
AC200mV/300mV/500mV/1V/2V/3V
1.交流電壓ACV:自動換檔10-600.0V
2.交流電流ACA:手動換檔20-6000A
20-1200A,精度:±0.5%FS(參閱型錄)
3.功率因素PF:0.01-1.00
4.相位角:-180°-180°
5.諧波顯示:1-50th
6.波峰因素:1.00-99.99
7.頻率:45-65Hz
8.功率Active(Real)Power:0-9.999MW
9.視在功率Apparent Power:0-9.999MVA
10.虛功率Reactive Power:0-9.999MVARH
11.瓦特小時WH:0-9999MWH
12.視在功率小時SH:0-9.999MVAH
13.虛功率小時QH:0-9.999MVAH
14.小時平均功率因素PFH
15.交流電流/電壓諧波幅度(1-50階)
16.交流電流/電壓諧波百分比(1-50階)
‧尺寸:225*125*64mm
‧使用電源:DC9V變壓器/三號電池*8
‧可選購電流勾頭:
CP-1201(標配)/CP-2000/CP-200
‧可搭配軟式比流器CT:CP-3000(選購)
(軟式環狀可繞式電流鉤頭)使用
FEATURE
1 Analysis for 3 phase multi-power system, 1P/2W, 1P/3W, 3P/3W, 3P/4W. Voltage and Current are the True RMS value.
2 3 current probes ( CP-1201 ) are included, if change the current probes, the calibration procedures are not necessary.
3 Current probe input signal/ranges with selection : Input signal (ACV) : 200 mV/300 mV/500 mV/1 V/2 V/3 V.
4 Ranges (ACA) : 20 A/200 A/2000 A/30 A/300 A/ 3000 A 60A/600A/6000A
5 Meter can cooperate the universal current probes.
6 Complete set with 4 PCs Test Leads, 4 PCs Alligator clips, 3 PCs Clamp Probe ( CP 1201 ), AC to DC 9V adapter, 2G SD memory card and Carrying bag.
7 Measurement : V (phase-to-phase), V (phase-to-ground) A (phase-to-ground) KW / KVA / KVAR / PF (phase) KW / KVA / KVAR / PF (system) KWH / KVAH / KVARH / PFH (system),Phase angle
8 Harmonics display (1-50th order).
9 Simultaneous display of Harmonics and Waveform.
10 Display of Waveform with Peak Values.
11 Analysis of Total Harmonic Distortion ( THD ).
12 Graphic Phase diagram with 3-Phase system parameters.
13 3 phase Voltage or Current Unbalanced Ratio ( VUR, AUR ) and Unbalanced Factor.
14 Calculated Unbalanced Current through Neutral Line ( An )
15 Capture Transient events (including Dip, Swell and Outage ) with programmable threshold ( % ).
16 Programmable CT ratio ( 1 to 600 ) and PT ratio ( 1 to 1000 ).
17 ACV input impedance is 10 Mega ohms.
18 Safety Standard : IEC 1010, CAT III 600V.
19 Built-in clock and Calendar, real time data record with SD memory card , sampling time set from 2 to 7200
20 seconds. Just slot in the SD card into the computer, it can down load the all the measured value with the time information ( year, month, data, hour, minute, second ) to the Excel directly, then user can make the further data analysis by themselves.
21 Powered by AA ( UM-3 ) DC 1.5 V X 8 batteries ( Alkaline type ) or DC 9V adapter.
22 Computer data output, can cooperate with optional USB Cable/USB-01, RS232 cable/UPCB-02 and Data Acquisition software, SW-811,SW-U811
23 Optional current probes : CP-1201, CP-2000, CP-200, CP-3000,CP-3001,CP-6001 detail specification.
24 User can order the meter only ( without the current probes ) with the special request as intend to cooperate their own current probes.